Skip to content
Klang IndustrialMs Teh Seok Hoon, PEA 4006

Sprinklers, hose reels, hydrants and alarms: Bomba requirements for a Klang factory or warehouse, and who pays

Ms Teh Seok Hoon, PEA 4006. Updated

A Klang factory or warehouse needs the fire systems that the building by-laws' Tenth Schedule sets for its use and floor area. Under the 2021 table, a single-storey factory needs hose reels from 750 m² and sprinklers above 2,000 m²; a warehouse of combustible goods needs sprinklers from 1,001 m² and 7,001 m³, plus a pressurised hydrant system above 10,000 m². Designated premises also need a yearly Fire Certificate. Your tenancy agreement decides who pays.

Key takeaways

  • Two rules apply: the Tenth Schedule of the building by-laws sets the systems by use and size, and the Fire Services Act 1988 sets the Fire Certificate and the duty to notify Bomba before changes.
  • Bomba has applied the 2021 table to plan submissions since 1 January 2023; older Klang buildings were approved under Selangor's 2012 table, so check what was approved for your unit.
  • Every building needs portable extinguishers and at least one fire hydrant nearby; hose reels, sprinklers and alarms depend on floor area, volume and whether the goods burn.
  • Covering, enclosing or tampering with a fire hydrant is an offence, which matters in truck and container yards around Kapar and Northport.
  • The Act makes the owner liable when a designated premises has no Fire Certificate, but the tenancy agreement decides who pays for servicing, repairs and upgrades: write each item down before you sign.
Factory and warehouse hall
Factory and warehouse hall · Illustrative image
Hose reels, single-storey factory (2021 table)
From 750 m²
Sprinklers, single-storey factory (2021 table)
Over 2,000 m²
Sprinklers, single-storey combustible goods warehouse (2021 table)
From 1,001 m² and 7,001 m³
Pressurised hydrant system added (warehouse, 2021 table)
Over 10,000 m² or 70,000 m³
Fire Safety Managers and Officers required
From 1 April 2027

Two rulebooks decide what a Klang unit needs

Every factory and warehouse in Klang, Kapar, Meru, Port Klang and Pulau Indah answers to two sets of rules. The building by-laws say which fire systems a building of a given use and size must have. The Fire Services Act 1988 says which premises need an annual Fire Certificate (Perakuan Bomba) and what must happen before such premises are changed.

Selangor has its own version of the by-laws. Its fire table, the Tenth Schedule, was last replaced as a whole by the Selangor Uniform Building (Amendment) (No. 2) By-Laws 2012, in force from 27 December 2012. On 31 December 2021 the Uniform Building (Amendment) By-Laws 2021 were gazetted with a rewritten table. In a circular dated 8 August 2024, Bomba's Director General said the National Council for Local Government agreed on 13 July 2021 to adopt the amendment, and that Bomba has enforced it nationwide since 1 January 2023, so architectural and M&E plans must meet its fire safety requirements.

In practice, a warehouse in Kapar or Pandamaran built ten years ago was checked against the older Selangor table, while a new building or a fresh submission today is checked against the 2021 one. For a tenant, the question is what was approved for that building and that use, and whether your goods, racking or partitions change it. The council's document checklist for a temporary licence (Lesen Sementara Industri) starts with Bomba's Klang zone (MBDK form); the other agencies are in her guide to the Klang council's factory and warehouse licence.

What the 2021 table asks for, by size and use

The 2021 table names each system by a letter or a number. The ones that matter in a Klang industrial estate are A (automatic sprinkler system), G (hose reel system), H (pressurised hydrant system), 1 (automatic fire detection), 2 (manual electric fire alarm), 4 (public address) and 6 (automatic fire monitoring). Separate by-laws say hose reels follow MS 1489, sprinklers MS 1910 and fire alarms MS 1745, and every building, whatever its size, must have portable fire extinguishers to MS 1539.

The rows below are for single-storey buildings (1 m² is about 10.76 sq ft). Use matters as much as size. A single-storey unit of about 680 m², the size of a 7,315 sq ft terrace factory in Pandamaran, needs no fixed system as a factory; used as a store for cartons or furniture, it falls in the 501 to 1,000 m² row for combustible goods: hose reels, automatic detection and a manual alarm. At the other end, a building the size of the 254,729 sq ft warehouse at Westport, about 23,700 m², sits in the top warehouse row. Hazardous areas such as boiler rooms, transformer rooms and indoor flammable liquid stores get whatever further protection the Director General requires.

  • Factory under 750 m² (about 8,070 sq ft): no fixed system or alarm in the table, only portable extinguishers.
  • Factory of 750 to 1,000 m²: hose reels and a manual fire alarm.
  • Factory of 1,001 to 2,000 m²: hose reels, automatic fire detection and a manual fire alarm.
  • Factory over 2,000 m² (about 21,500 sq ft): automatic sprinklers and hose reels, with a manual fire alarm, public address and automatic fire monitoring.
  • Warehouse of combustible goods: nothing under 250 m²; a manual alarm from 250 to 500 m²; hose reels, detection and alarm from 501 to 1,000 m² (under 7,000 m³); sprinklers, hose reels, alarm and fire monitoring from 1,001 to 10,000 m² and 7,001 to 70,000 m³.
  • Warehouse of combustible goods over 10,000 m² or 70,000 m³: a pressurised hydrant system is added to the sprinklers and hose reels.
  • Warehouse of non-combustible goods such as clay: nothing under 2,000 m² on one floor, hose reels and a manual alarm above it.

Buildings approved before 2023: Selangor's 2012 table

A unit approved before 2023 was checked against Selangor's 2012 table, and its letters mean different things: A is a hose reel system, B sprinklers, C a gaseous system and D a pressurised fire hydrant. A plan from that era marked A and B therefore means hose reels and sprinklers, not sprinklers and water spray.

Its single-storey factory rows are close to the 2021 ones: nothing under 750 m²; 25 kg trolley extinguishers and an alarm item from 750 to 1,000 m²; hose reels from 1,001 m²; hose reels and sprinklers above 2,000 m², with a fire command centre among the alarm items. For a single-storey warehouse of combustible goods, hose reels came in from 501 m², and sprinklers once the floor passed 1,000 m² or the volume passed 7,000 m³. The 2012 table has no pressurised hydrant row for warehouses; the 2021 table adds one above 10,000 m² or 70,000 m³.

The hydrant rule moved too. Selangor's 2012 by-law asks for at least one hydrant within 45 metres of the fire brigade access, with hydrants no more than 90 metres apart. The 2021 by-law asks for one within 30 metres of an entry to the building or of the breeching inlet, also no more than 90 metres apart, designed and installed to MS 1489. If your fit-out needs a new submission, ask the landlord's engineer which table Bomba will apply and what closing the gap would cost before you commit.

When the unit also needs a Fire Certificate

Section 28 of the Act says every designated premises needs a Fire Certificate, renewable every year. Factories and storage buildings are two of the nine categories of designated premises, Bernama reported in August 2025; Bomba's Designated Premises Order decides which factories and warehouses fall in by size, so ask the landlord whether the unit is designated and to see the current certificate. Bomba's deputy director-general (operations) said then that full enforcement would start in the first quarter of 2026, with fines of up to RM50,000, five years' jail or both for premises without one, and that every premises receiving a Certificate of Completion and Compliance (CCC) must register for the certificate. At that time 9,321 premises nationwide were designated and 5,881 held a certificate.

Selangor has its own gaps. In April 2024 the state Fire and Rescue Department director said about 10% (190 out of 1,900) of Selangor buildings with certificates had failed to meet the requirements, The Star reported.

The rules are getting stricter. The Fire Services (Amendment) Bill 2025 passed the Dewan Rakyat on 5 March 2025; it puts the duty to set up a fire safety organisation on premises owners or managers, and brings in registration of fire safety consultants, competent persons, fire safety contractors and fire safety installations. From 1 April 2027, owners of 9,451 designated buildings must appoint Fire Safety Managers and Fire Safety Officers, Bomba's director-general said in October 2026 (Malay Mail), with six to 18 months to prepare depending on when the current certificate expires. The managers' annual inspection reports will then be assessed for renewal, and in August 2025 he said, in remarks carried by NADMA, that periodic inspections will still be carried out every two to three years.

Changes count as well. Under section 32 of the Act, as printed in the official reprint, the occupier of a designated premises must give Bomba notice before starting a material change while a certificate is in force, and starting without notice is an offence. Bomba can then set the steps needed to keep the fire systems adequate. Taller racking, a mezzanine, new partitions or a switch to more combustible goods can all change what the sprinklers, detectors and exits must cover; see her guide on pallet racking and Bomba checks.

Checks at a viewing in Kapar, Port Klang or Pulau Indah

Recent fires around Klang show why the water supply and the systems matter. In March 2026 a vehicle workshop, a recycling factory and a paint warehouse burned in Kampung Perepat, Klang; two were completely destroyed, 31 officers and personnel from six stations including Kapar, Klang Utara and Port Klang were deployed, and the Bomba officer noted the absence of an open water source at the location (The Sun). In September 2026 about 70% of a two-storey furniture storage warehouse on Jalan Perusahaan 22, Kampung Idaman, Port Klang was affected (NST). The same month, two plastic waste warehouses in Section 32, Shah Alam were destroyed, and an initial inspection found the premises had no fire safety system (Malay Mail).

So look past the floor area. FactoryHub's pages for the Kapar and Sungai Kapar Indah industrial area and Pulau Indah Industrial Park (PIIP) list units with built-up area and ceiling height, the two numbers that place a building in the table. On site, check these yourself:

  • Find the nearest fire hydrant and the breeching inlet, and pace the distance to the main entry (30 metres under the 2021 by-law; 45 metres from the fire brigade access under the 2012 Selangor rule).
  • Look around the hydrant: under section 26 of the Act, covering up, enclosing or concealing a hydrant, tampering with it, or using it other than for fire fighting is an offence, so trailers, containers and pallets must stay clear. In container and haulage yards near Northport, works that affect a hydrant or the flow of water to it need written notice to the State Director at least seven days ahead (section 23).
  • Open the pump room: sprinkler and hose reel pumps, tank level, valves, and the date of the last service report.
  • Walk to each hose reel: the drum should be reachable, not boxed in by stock or racking.
  • Check that the alarm panel shows no faults, and that detectors and manual call points are still in place after past renovations.
  • Read the tags on the portable extinguishers and count them against the floor.
  • Ask which rooms count as hazardous areas (boiler, transformer, switch room, flammable liquid store) and what protection Bomba approved for them.

Who pays in a tenancy

The Act puts the legal duties in a few places. Where a designated premises has no Fire Certificate in force, section 33 makes the owner guilty of an offence, and the Act defines the owner first as the registered proprietor; only where no proprietor, agent, trustee or personal representative exists is it the person receiving the rent. An application can be made by the owner, the occupier or the person having overall management of the premises (section 29). The duty to notify Bomba before a material change sits with the occupier (section 32).

Before you sign, ask for the approved fire plans, the current certificate if the unit is designated, the last service reports, and a joint test of the pumps and alarm at handover, recorded on the handover list. If Bomba later asks for changes, those records show what was working on the day you took the keys.

The money is a matter for the tenancy agreement, and silence leads to disputes. After a fire at four factories in Gelang Patah, Johor in October 2024, Utusan Malaysia reported that a tenant company was running other Johor factories whose Fire Certificates had expired. The owner of one of them said the tenant was ultimately responsible for these approvals under the tenancy agreement, while Bomba restated that without a certificate it is the owner of the premises who commits the offence. Both sides carried the risk. Settle each cost line in writing before you sign:

  • The yearly Fire Certificate renewal and inspection, and from April 2027 the Fire Safety Manager and Officers and their annual report.
  • Routine servicing of extinguishers, hose reels, sprinkler pumps and the alarm panel, by registered fire safety contractors.
  • Repair or replacement of major parts such as the fire pump, the tank or the alarm panel.
  • Upgrades Bomba asks for because of the tenant's racking, goods or partitions, as against upgrades the building needed anyway.
  • The automatic fire monitoring link to Bomba, where the table or the certificate requires one.
  • Reinstatement of any fire system changes when the lease ends.

Emergency exits, upgrade costs and a building that falls short

How many emergency exits does a factory need?

The number comes from the building by-laws' travel distance and occupancy rules for that building, and it is fixed on the fire plans Bomba approved for it. So ask for the approved fire plans and walk them: every exit shown must still exist, open outwards where required and stay clear. In Klang units the common failure is racking, stock or a new partition blocking an exit route after the plans were approved.

How much does it cost to upgrade a factory's fire protection in Klang?

There is no standard figure: it depends on the gap. Adding hose reels or an alarm to a small unit is a different job from adding sprinklers, a pump room and tanks to a warehouse that crossed 1,001 m² of combustible storage. Get the gap list from a Bomba-registered consultant, then itemised quotes from registered fire safety contractors, and settle in the tenancy which upgrades are the owner's and which are yours.

What should I do if a Klang factory's fire protection does not meet the rules?

First find which rulebook applies: the fire table for the building's approved use and size, Selangor's 2012 table for buildings approved before 2023, and the Fire Certificate rules if the premises are designated. Have a Bomba-registered fire consultant list the gaps, then agree in writing who fixes what. Gaps caused by the tenant's racking, goods or partitions are usually the tenant's; gaps the building had anyway are the owner's.

Finding a unit that fits your goods

Fire systems are easier to settle before the offer than after the keys change hands. If you are comparing warehouses or factories in Kapar, Meru, Port Klang or Pulau Indah, Ms Teh can help you shortlist units by floor area, height and use, and ask landlords for their fire plans and certificates before the first viewing.

Questions buyers and tenants ask

What is the Bomba hose reel requirement for a factory or warehouse?

Under the 2021 table, a single-storey factory needs a hose reel system from 750 m², and a single-storey warehouse of combustible goods from 501 m², installed to MS 1489 (by-law 226a). Older Selangor buildings followed the 2012 table, where factories needed hose reels from 1,001 m², so check the approved plans of the unit you are looking at.

Does a 20,000 sq ft warehouse in Klang need sprinklers?

20,000 sq ft is about 1,858 m². Storing combustible goods on one floor, it is above 1,001 m², and at a height of 7.5 m its volume is about 13,900 m³, so the 2021 table asks for sprinklers and hose reels, a manual alarm and automatic fire monitoring. Under Selangor's 2012 table it also fell in the sprinkler row, being over 1,000 m². Non-combustible goods such as clay follow a lighter row.

Is Sijil Perakuan Bomba the same as a Bomba fire certificate (FC)?

Yes. Perakuan Bomba is the Fire Certificate under section 28 of the Fire Services Act 1988, needed by designated premises and renewed every year. It is different from the approval of the fire system plans, and from the Bomba document MBDK asks for in an industrial licence application.

Who pays if the fire pump fails during my tenancy?

The Act does not say; the tenancy agreement does. The Act makes the owner liable if a designated premises has no certificate, and Bomba issues a certificate only when satisfied the fire protection is adequate (section 29). Write down whether major parts such as pumps, tanks and alarm panels are the landlord's repair and routine servicing the tenant's, or the other way round, and keep the service reports.

Do I need to tell Bomba before installing racking or a mezzanine?

If the unit holds a Fire Certificate and the change is material, yes: section 32 requires the occupier to give notice before work starts, and starting without notice is an offence. Bomba may set the steps needed to keep the fire systems adequate, then amend the certificate or issue a new one.

Are the rules different in Pelabuhan Klang (Port Klang) or Pulau Indah?

The Fire Services Act is national law, and Klang district follows the same Selangor building by-laws; what differs is the building, its approval date and its use. If the unit sits inside a port or free zone area, ask the landlord which authority approved the building plans. In truck and container yards, keep hydrants clear: concealing or tampering with one is an offence under section 26.

Units in these places

Tell Ms Teh what you need

Send the size, power, ceiling height, budget and move-in date you need on WhatsApp, or call her directly.

WhatsApp Ms TehCall